MACROMATIC PMP575 Image 1

MACROMATIC PMP575 3PH 460-600V 10A SPDT PLUG IN MONITOR RELAY

MFR Part #: PMP575
SKU #: 1264749
Brand: MACROMATIC
UPC: 400051091963
MACROMATIC PMP575 3-phase Monitor Relay, 575 VAC, 8 pin plug-in, 10 Amp SPDT relay, phase loss, reversal - fixed, unbalance, over/under voltage - adjustable
UL Recognized Component (cURus, File #E109466) | UL Listed (cULus, File #E109466 with appropriate socket) | CE Marked (EN60947-1, EN60947-5-1)

MACROMATIC PMP575 3-phase Monitor Relay, PMP Series, SPDT 10 A at 277V AC / 7 A at 30V DC ; 1 hp at 250V AC, 1/2 hp at 125V AC Contact Rating, Mechanical Life of 10000000 operations, Operating Temp of -28 to 65 deg C, Storage Temp of -40 to 85 deg C, 40 VA Power Consumption, 460-600 V Rating

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. As standard, re-energization is automatic upon correction of the fault condition. Manual reset is available if an external momentary N.C. switch is connected to pins 6 and 7. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.

Product Details

MACROMATIC PMP575 3-phase Monitor Relay, PMP Series, SPDT 10 A at 277V AC / 7 A at 30V DC ; 1 hp at 250V AC, 1/2 hp at 125V AC Contact Rating, Mechanical Life of 10000000 operations, Operating Temp of -28 to 65 deg C, Storage Temp of -40 to 85 deg C, 40 VA Power Consumption, 460-600 V Rating

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. As standard, re-energization is automatic upon correction of the fault condition. Manual reset is available if an external momentary N.C. switch is connected to pins 6 and 7. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.

Attributes

Contact RatingSPDT 10 A at 277V AC / 7 A at 30V DC ; 1 hp at 250V AC, 1/2 hp at 125V AC
SeriesPMP Series
Voltage Rating460-600 V
Mechanical Life10000000 operations
Operating Temperature-28 to 65 deg C
Power Consumption40 VA
Storage Temperature-40 to 85 deg C

Features

  • Protects against phase loss, phase reversal, phase unbalance, undervoltage, overvoltage & rapid cycling
  • True RMS voltage measurement ensures accurate sensing across more applications
  • Retains fault indication and continues monitoring all voltages even with a lost phase
  • Ultimate three-phase protection with a variety of user-selectable and adjustable settings
  • Full fault indication on top of unit for easy troubleshooting
  • Manual reset option works with external switch to reset the relay from outside the enclosure